Parameter
Description
Factory setting
EHC–04
Factory setting
SCB-04
AP063
Maximum flow temperature setpoint for burning at central heating
Can be set from 20 °C to 90 °C
Hydraulic back-
up: 90
Electrical back-
up: 75
not available
AP075
Outdoor temperature neutral band between heating and cooling. The
generator is stopped.
Can be set from 0 to 10 °C
4
4
AP079
Inertia of the building used for heat up speed
Can be set from 0 to 10
0 = 10 hours for a building with low thermal inertia,
= 22 hours for a building with normal thermal inertia,
10 = 50 hours for a building with high thermal inertia.
Modification of the factory setting is only useful in exceptional cases.
3
3
AP080
Outside temperature below which the antifreeze protection is
activated:
can be set from -29 to 20 °C
set to -30 °C = function deactivated
3
3
AP091
Outdoor sensor type
0 =Auto
0
-
AP098
Blocking input 1 contact direction configuration
0 = input active on Open contact
1 = input active on Closed contact
1
not available
AP099
Blocking input 2 contact direction configuration
0 = input active on Open contact
1 = input active on Closed contact
1
not available
AP100
Blocking input 2 setting
1 = Full blocking of the installation – frost protection not guaran
teed
2 = Partial blocking of the installation – frost protection active
3 =User reset locking
4 =Backup Relieved
5 =Heat Pump Relieved
6 =HP & backup relieved
7 =High, Low Tariff
8 =Photovoltaic HP Only
9 =PV HP And backup
10 =Smart Grid ready
11 =Heating Cooling
2
not available
HP : Heat-pump Parameters = Heat pump parameters
Tab.44
Parameter
Description
Factory setting
EHC–04
HP000
Outside bivalence temperature
Bivalence temperature above which only heat pump is allowed
10
HP054
COP threshold above which heat pump is authorized to operate when hybrid
mode is primary energy
Can be set from 1 to 5 °C
Value accepted when HP061=2
2.5
10 Settings
7685645 - v04 - 07032018
AWHP-2 iMPI
81