Fig.23
Distances of the appliance from the wall
MW-M001450-1
G
F
F
G
A
C
B
B
C
E
A
1000
D
Max.
500
Max.
500
Tab.17 Minimum dimensions in mm
AWHP 4.5 MR
AWHP 6 MR-3
AWHP 8 MR-2
AWHP 11 MR-2
AWHP 16 MR-2
AWHP 11 TR-2
AWHP 16 TR-2
A
100
150
B
500
1000
C
200
300
D
1000
1500
E
300
500
F
150
250
G
100
200
Position of the outdoor unit
Carefully choose the position of the outdoor unit in relation to neighbours
as it is a source of noise.
Warning
Nothing must obstruct the free circulation of air around the out
door unit (intake and outlet).
Do not place the outdoor unit close to where people sleep.
Do not place the unit opposite a wall with windows.
Avoid placing it close to a terrace, etc.
Choose a location away from prevailing winds.
Ensure sufficient above ground elevation (100 to 500 mm) to keep it above
water.
Always use a base with a metal frame sufficiently high off the ground to
allow correct condensates discharge. The width of the base must not ex
ceed the width of the outdoor unit.
Always install the outdoor unit sufficiently high off the ground to allow cor
rect condensates discharge.
Fig.24
Position of the outdoor unit
MW-M001448-2
5 Before installation
7685645 - v04 - 07032018
AWHP-2 iMPI