Important
The condensates discharge must be regularly cleaned in order to
prevent any blockages.
5.4
Fitting the outdoor sensor
1. Choose the optimum location for the outdoor sensor.
2. Put the 2 plugs in place, delivered with the sensor (diameter 4 mm).
3. Secure the sensor using the screws provided (diameter 4 mm).
4. Connect the cable to the outdoor temperature sensor.
5.4.1
Recommended positions
Place the outside sensor in a position that covers the following character
istics:
On a façade of the area to be heated, on the north if possible.
Half way up the wall of the area to be heated.
Under the influence of changes in the weather.
Protected from direct sunlight.
Easy to access.
Fig.26
MW-8800N001-3
2
1
2
1
1
2
H
1/2 H (min. 2,5 m)
1/2 H (min. 2,5 m)
1/2 Z
H
Z
1 Recommended position
2 Possible position
H Inhabited height controlled by the sensor
Z Inhabited area controlled by the sensor
5.4.2
Positions to be avoided
Avoid placing the outside sensor in a position with the following character
istics:
Masked by part of the building (balcony, roof, etc.).
Close to a disruptive heat source (sun, chimney, ventilation grid, etc.).
Fig.25
Mounting the outdoor sensor
MW-8800N003-6
2
3