Tab.24 Outdoor unit
Unit
AWHP
4.5 MR
AWHP 6
MR-3
AWHP 8
MR-2
AWHP 11
MR-2
AWHP 11
TR-2
AWHP 16
MR-2
AWHP 16
TR-2
Power supply type
Single
phase
Single
phase
Single
phase
Single
phase
Three
phase
Single
phase
Three
phase
Cross section of the power sup
ply cable
mm²
3 x 2.5
3 x 2.5
3 x 4
3 x 6
5 x 2.5
3 x 10
5 x 2.5
Circuit breaker curve C
A
20
16
25
32
16
40
16
Maximal amperage
A
12
13
19
28
13
29
13
Tab.25 Indoor module
Cross section of the power supply cable
mm²
3 x 1.5
Circuit breaker curve C
A
10
BUS cable cross section
(1)
mm²
2 x 1.5
(1) Connection cable linking the outdoor unit to the indoor module
Tab.26 Connecting the electrical back-up
Unit
Single phase
Three phase
Cable cross section
mm²
3 x 6
5 x 2.5
Circuit breaker curve C
A
32
16
7.5.5
Accessing the PCBs and connection terminal block
1. Remove the front panel by pulling firmly upwards.
2. Remove the plate concealing the PCBs.
Fig.57
MW-3000546-01
2
1