Parameter
Description
Factory setting
EHC–04
HP061
Hybrid mode management:
0 =No Hybrid
1 =Hybrid Cost
2 =Primary Energy
3 =Hybrid CO2
1
HP065
Electrical CO2 emission in heating mode
Can be set from 0 to 100 (x0.01)
Value accepted when HP061=3
18
HP066
Electrical CO2 emission in DHW mode
Can be set from 0 to 100 (x0.01)
Value accepted when HP061=3
4
HP067
Gas or Oil CO2 emission
Can be set from 0 to 100 (x0.01)
Value accepted when HP061=3
23
HP068
Boiler in appliance efficiency
Can be set from 0 to 100%
100
PP015
Central heating pump post run time
Post-circulation of the heating pump:
can be set from 0 to 98 minutes
set to 99 = runs continuously
3
AD
Auto detect
available
CNF
Reset factory parameters
See the data plate.
ADV
ADV advanced parameters
not available
10.2.6 Installer \EHC–04 and SCB-04\ADV menu
AP : Appliance Parameters = Appliance parameters
ADV
Description of the ADV advanced parameters
Factory setting
EHC–04
Factory setting
SCB-04
AP002
Enable manual heat demand function
In this mode, the temperature set point used will be that for the
AP026 parameter.
0
AP006
Appliance will report low water pressure below this value
Can be set from 0 bar to 6 bar
0.3
not available
AP009
Burning hours before raising a service notification
Can be set from 0 to 65534 hours
17400
not available
AP010
Service:
0 =None
1 =Custom notification
2 =ABC notification
0
not available
AP011
Hours powered to raise a service notification
Can be set from 0 to 65534 hours
17400
not available
AP026
Flow temperature setpoint for manual heat demand
Can be set from 7 to 80°C
Set point used when manual mode is active (AP002 = 1)
40
not available
AP058
Warning message indicating that pressure is low
Can be set from 0 bar to 2 bar
0.8
not available
10 Settings
82
AWHP-2 iMPI
7685645 - v04 - 07032018