Tab.42 List of ADV parameters in the sub-menu of the Installer menu
ADV
Description of the ADV advanced parameters
Factory setting
DP004
Legionella mode protection calorifier
0 =Disabled
1 = on: the domestic hot water tank is superheated to 65 °C for 20 minutes
once a week.
2 = automatic: the domestic hot water tank is remotely controlled.
0
DP046
Maximum domestic hot water temperature
Can be set from 10 °C to 70 °C
70
DP047
Maximum time allowed to produce Domestic Hot Water
Can be set from 1 to 10 hours
3 (4.5 kW - 6 kW - 8
kW)
2 (11 kW - 16 kW)
DP048
Minimum heating time before Domestic Hot Water production
Can be set from 0 to 10 hours
2
DP055
Enable/disable the TAS protection of the DHW tankCan be set from 0 to 1
0
DP090
Delay for starting the next generator (backup stage) in DHW mode
Can be set from 0 Min to 120 Min
90
DP100
Delay for stopping the next generator (backup stage) in DHW mode
Can be set from 0 Min to 120 Min
2
DP110
Delay for starting the next generator (backup stage) in DHW mode
Can be set from 0 Min to 255 Min
5
DP150
Enable DHW Thermostat function
0 =Off
1 =On
1
DP160
Setpoint for DHW anti legionella
Can be set from 60 °C to 90 °C
Do not modify this setting
65
10.2.5 Installer \EHC–04 and SCB-04 menu
AP : Appliance Parameters = Appliance parameters
Tab.43
Parameter
Description
Factory setting
EHC–04
Factory setting
SCB-04
AP001
Blocking input setting (1: Full blocking, 2: Partial blocking, 3: User
reset locking) BL1:
1 = Full blocking of the installation – frost protection not guaran
teed
2 = Partial blocking of the installation – frost protection active
3 =User reset locking
4 =Backup Relieved
5 =Heat Pump Relieved
6 =HP & backup relieved
7 =High, Low Tariff
8 =Photovoltaic HP Only
9 =PV HP And backup
10 =Smart Grid ready
11= heating/cooling
2
not available
AP028
Defines the type of cooling used.
0 =Off
1 =Active cooling on
2 = Free cooling on, not used
0
1
10 Settings
80
AWHP-2 iMPI
7685645 - v04 - 07032018