ADV parameter
Description of the ADV advanced parameters
Factory setting
EHC–04
HP047
Maximum time at maximum outside temperature to start back up in CH mode
when dynamic timer selected
Can be set from 1 to 10 minutes
Value accepted when HP031 = 0
8
HP048
Maximum time at maximum outside temperature to start back up in CH mode
when dynamic timer selected
Can be set from 0 to 60 minutes
Value accepted when HP031 = 0
30
HP049
Minimum outside temperature for dynamic timer when dynamic mode is selected
Can be set from -30 to 0 °C
Value accepted when HP031 = 0
-10
HP050
Maximum outside temperature for dynamic timer when dynamic mode is
selected
Can be set from -30 to +20 °C
Value accepted when HP031 = 0
15
HP051
Minimum operating temperature for the heat pump
Can be set from -20 to +5 °C
-15 °C for 4.5 kW
-15 °C for 6 kW
-20 °C for 8 kW
-20 °C for 11 kW
-20 °C for 16 kW
HP058
Enabling Heat pump Silent mode
0 =No
1 =Yes
Requires a specific option. Not available for AWHP 4.5 MR.
0
HP069
Heat Pump flow speed set-point depending on Heat Pump Power configuration
Can be set from 0 to 100 l/min
12 for 4.5 kW
17 for 6 kW
23 for 8 kW
32 for 11 kW
46 for 16 kW
HP079
Maximum offset applied on the dynamic cooling setpoint when a 0-10V humidity
sensor is used
Can be set from 0 to 15°C
5
HP086
Activation of hydraulic management mode for the configuration with a low-loss
header, or for a buffer tank connected as a low-loss header
0 =No
1 =Yes
0
HP087
Buffer tank hysteresis to start and stop heating
Can be set from 0 to 30 °C
6
HP091
Offset temperature of heating setpoint when photovoltaic function is activated
Can be set from 0 to 30 °C
0
HP092
Offset temperature of DHW setpoint when photovoltaic function is activated
Can be set from 0 to 30 °C
0
HP094
Start time of the low noise when option activated
Can be set from 00:00 to 23:59
Value accepted when HP058 = 1
22:00
HP095
Stop time of the low noise when option activated
Can be set from 00:00 to 23:59.
Value accepted when HP058 = 1
06:00
HP108
Activation time delays for the back-ups between stage 1 and stage 2 (electrical
back-up) in central heating mode
4
10 Settings
84
AWHP-2 iMPI
7685645 - v04 - 07032018