Product name
AWHP-2 iMPI
AWHP 8 MR-2
AWHP-2 iMPI
AWHP 11
MR-2
AWHP 11
TR-2
AWHP-2 iMPI
AWHP 16
MR-2
AWHP 16
TR-2
Seasonal space heating energy efficiency under
average conditions
ƞ
s
%
129
125
121
Seasonal space heating energy efficiency under
colder conditions
ƞ
s
%
119
113
113
Seasonal space heating energy efficiency under
warmer conditions
ƞ
s
%
169
167
161
Declared coefficient of performance or primary
energy ratio for part load at an indoor tempera
ture of 20°C and outdoor temperature
T
j
T
j
= -7°C
COPd
-
1.95
1.87
1.85
T
j
= +2°C
COPd
-
3.22
3.17
3.02
T
j
= +7°C
COPd
-
4.57
4.54
4.34
T
j
= +12°C
COPd
-
6.55
6.19
5.75
T
j
= bivalent temperature
COPd
-
1.70
1.20
1.35
T
j
= operation limit temperature
COPd
-
1.70
1.20
1.35
Operation limit temperature for air-to-water
heat pumps
TOL
°C
-10
-10
-10
Heating water operating limit temperature
WTOL
°C
60
60
60
Electrical power consumption
Off mode
P
OFF
kW
0.009
0.009
0.009
Thermostat-off mode
P
TO
kW
0.049
0.023
0.035
Stand-by
P
SB
kW
0.014
0.023
0.023
Crankcase heater mode
P
CK
kW
0.055
0.055
0.055
Supplementary heater
Rated heat output
Psup
kW
0.0
0.0
0.0
Type of energy input
Electricity
Electricity
Electricity
Other specifications
Capacity control
Variable
Variable
Variable
Sound power level, indoors - outdoors
L
WA
dB
49 – 67
48 – 69
48 – 70
Annual energy consumption under average
conditions
Q
HE
kWh
3499
3999
5861
Annual energy consumption under colder con
ditions
Q
HE
kWh
4621
3804
5684
Annual energy consumption under warmer
conditions
Q
HE
kWh
1904
2580
4120
Rated air flow rate, outdoors for air-to-water
heat pumps
—
m
3
/h
3300
6000
6000
(1) The rated heat output
Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
(2) If
Cdh is not determined by measurement, the default degradation coefficient is Cdh = 0.9.
See
The back cover for contact details.
3 Technical specifications
7685645 - v04 - 07032018
AWHP-2 iMPI