6-6
BE1-BPR Communications
Purpose:
Reads a listing of all fault records, reads summary information about any individual fault
record or clears all fault records.
Syntax:
FLOG[#][=0]
Reference:
Section 4,
Functional Description, Fault Log (Enhanced Relays Only), Fault Log Listing
FLT Command
(Enhanced Relays Only)
Purpose:
Obtains a COMTRADE report.
Syntax:
FLT<#><type>
Reference:
Section 4,
Functional Description, Fault Log , Oscillographic Data Acquisition
FREQ Command
Purpose:
Reads or changes the nominal power system frequency information used by the relay.
Syntax:
FREQ[=<freq(hz)>]
Reference:
Section 4,
Functional Description, Maintenance, Calibrating the Analog Channels
HELP Command
Purpose:
Obtains helpful information about communication port commands.
Syntax:
HELP[x/<cmd>]
Reference:
Section 4,
Functional Description, Software Functional Description, Introduction
I Command
Purpose:
Reads the primary current value of all or individual phases.
Syntax:
I[<phase>]
Reference:
Section 4,
Functional Description, Software Functional Description, Relay Status
ID Command
Purpose:
Reads or programs a relay ID number for polled communication.
Syntax:
ID [=<id(0-255)>]
Reference:
Section 4,
Functional Description, Software Functional Description, Maintenance,
Communication Settings
LF Command
Purpose:
Reads or changes the fault detector logic of the active logic scheme.
Syntax:
LF[x][=<type>,<filter>]
Reference:
Section 4,
Functional Description, Software Functional Description, Relay Setup, Fault
Detectors
LI Command
Purpose:
Reads or programs contact input logic.
Syntax:
LI [#[=<r>,<db>]]
Reference:
Section 5,
BESTlogic Programmable Logic, Input Contact Logic, Definition of Input Contact
Operation
LINFO Command
Purpose:
Reads the names of all logic schemes in memory or the equations associated with the
named logic scheme.
Syntax:
LINFO[<name>]
Reference:
Section 5,
BESTlogic Programmable Logic, General
LN Command
Purpose:
Reads the name of the active logic or program a new set of logic equations called <name>.
Syntax:
LN[=<name>]
Reference:
Section 5,
BESTlogic Programmable Logic, Logic Names
LO Command
Purpose:
Reads or programs output logic.
Syntax:
LO [#[=<Boolean equation>]]
Reference:
Section 5,
BESTlogic Programmable Logic, Programming Output Operational
Characteristics
LOGIC Command
Содержание BE1-BPR
Страница 1: ...Publication 9 2720 00 990 Revision E 12 98 INSTRUCTION MANUAL for BE1 BPR BREAKER PROTECTION RELAY...
Страница 31: ...BE1 BPR Application 2 17...
Страница 41: ...BE1 BPR Human Machine Interface 3 3 Figure 3 3 BE1 BPR Relay Horizontal Mount Front And Rear Views...
Страница 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Страница 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Страница 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Страница 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Страница 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Страница 120: ...7 2 BE1 BPR Installation Figure 7 1 Overall Dimensions Figure 7 2 Cutout Dimensions Panel Mount...
Страница 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Страница 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Страница 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...