BE1-BPR BESTlogic
5-17
CUSTOM APPLICATION EXAMPLES
Breaker Failure Logic For Breakers With Pre-Insertion Resistors (BFRES)
BFRES logic is an example of an adaptive breaker resistor protection scheme that allows more time for the
fault to clear once the breaker resistor has reduced the fault current. For more information, refer to Section 2,
Breaker Failure Protection With Pre-Insertion Resistors.
LN=BFRES
LF1=PI,1
LF2=NI,1
LF3=PI,2
LI1=4,12
LI2=4,12
LI3=4,12
LI4=4,12
LI5=4,12
LI6=4,12
LI7=4,12
LR=0,0,0,0,0
LT1=D,O8,/O8
LT2=D,O8,/O8
LT3=0,0,0
LT4=D,O6,/O6
LT5=0,0,0
LT6=0,0,0
LOA=T4+O15
LO1=T1O7+T2F3
LO2=T1O7+T2F3
LO3=T1O7+T2F3
LO4=O14
LO5=O8
LO6=/I1/I2
LO7=F1+F2
LO8=I3+I4+I5
LO9=0
LO10=0
LO11=0
LO12=F3I1
U
U
The non-maskable alarms are always ORed with the programmable diagnostics to provide an alarm
output.
Содержание BE1-BPR
Страница 1: ...Publication 9 2720 00 990 Revision E 12 98 INSTRUCTION MANUAL for BE1 BPR BREAKER PROTECTION RELAY...
Страница 31: ...BE1 BPR Application 2 17...
Страница 41: ...BE1 BPR Human Machine Interface 3 3 Figure 3 3 BE1 BPR Relay Horizontal Mount Front And Rear Views...
Страница 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Страница 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Страница 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Страница 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Страница 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Страница 120: ...7 2 BE1 BPR Installation Figure 7 1 Overall Dimensions Figure 7 2 Cutout Dimensions Panel Mount...
Страница 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Страница 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Страница 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...