BE1-BPR Functional Description
4-9
Changing Parameters Using Communication Ports
Changing settings through a communication port requires an ACCESS-CHANGE-SAVE-CONFIRM cycle.
The operator uses the ACCESS command to obtain a program (change) access level. Different passwords
give access to change different parameters.
ACCESS
Programming changes access
HMI Menu Branch: N/A
Comments
This command is used to gain access to an access area before making programming or
settings changes. The access areas available are:
ACCESS AREA 1: Access is provided by password 1 (PW1). PW1 allows write access to
all setting and operating registers with no restrictions.
ACCESS AREA 2: Access is provided by password 2 (PW2). PW2 permits changes to be
made to relay protection settings.
ACCESS AREA 3: Access is provided by password 3 (PW3). PW3 allows breaker related
settings changes to be made.
ACCESS AREA 4: Access is provided by password 4 (PW4). PW4 allows control or relay
outputs for testing purposes.
Access to an area is granted when the appropriate password is entered. If password
protection is disabled in one or more areas, then no password is required to gain access to
the unprotected levels. If a valid password is entered, the relay responds with the access
area provided by that password. If an invalid password is entered, an error message is
returned.
ACCESS Command
Purpose:
Reads or changes access area so that programming or settings changes can be made.
Syntax:
ACCESS[=<password>]
ACCESS Command Examples
1.
Obtain area two access.
ACCESS=OPENUP
ACCESS GRANTED
AREA 2
2.
Read the current programming access area.
ACCESS
AREA 2
After the change(s) are made, the new data must be saved using the SAVE command. The operator must
confirm that the programming is completed before the changes are actually made. If no password protection
is used, it is still necessary to obtain programming/change access in order to protect against accidental
changes. If password protection is disabled then ACCESS=BPR or any other string will be accepted in place
of a password.
SAVE
Exit programming mode and save changes
HMI Menu Branch: N/A
Comments
This command is used at the end of a programming or settings changing session to save
the changes made. When the SAVE command is entered, the relay responds with a
confirmation message (ARE YOU SURE (Y/N)?). If Y is entered, programming or settings
changes are saved to non-volatile memory, the programming mode is exited, and the relay
is returned to an on-line condition. Entering N exits the programming mode without saving
changes and returns the relay to an on-line condition.
Содержание BE1-BPR
Страница 1: ...Publication 9 2720 00 990 Revision E 12 98 INSTRUCTION MANUAL for BE1 BPR BREAKER PROTECTION RELAY...
Страница 31: ...BE1 BPR Application 2 17...
Страница 41: ...BE1 BPR Human Machine Interface 3 3 Figure 3 3 BE1 BPR Relay Horizontal Mount Front And Rear Views...
Страница 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Страница 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Страница 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Страница 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Страница 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Страница 120: ...7 2 BE1 BPR Installation Figure 7 1 Overall Dimensions Figure 7 2 Cutout Dimensions Panel Mount...
Страница 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Страница 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Страница 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...