Figure 499:
Angle difference when power transformer is in sychrocheck zone
The vector group of the power transformer is defined with clock numbers, where the value
of the hour pointer defines the low-voltage-side phasor and the high-voltage-side phasor
is always fixed to the clock number 12, which is same as zero. The angle between clock
numbers is 30 degrees. When comparing phase angles, the
V_BUS
input is always the
reference. This means that when the Yd11 power transformer is used, the low-voltage-
side voltage phasor leads by 30 degrees or lags by 330 degrees the high-voltage-side
phasor. The rotation of the phasors is counterclockwise.
The generic rule is that a low-voltage-side phasor lags the high-voltage-side phasor by
clock number * 30º. This is called angle difference adjustment and can be set for 25 with
the
Phase shift
setting.
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
985
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......