GUID-3C167F6E-E0BF-4AC6-B059-7FBFE5AAD307 V1 EN
Figure 342:
Operating region for out of step with double blinder
An impedance is only considered to be within the mho circle if it is also
between the inner blinders.
A third zone, Zone 3, can be enabled by setting
Zone 3 enable
to “Yes”. Zone 3 is defined
to include the area outside of the circular mho characteristic but inside the area that is
bound with the magnitude of the minimum positive-sequence current defined by setting
Min Ps Seq current
and the rated positive-sequence voltage.
Figure
shows the three zones.
Settings that determine the shape of the zones should be coordinated with the settings for
any distance protection functions. The zones and their respective slip counters are
applicable only for Way out operations when the
Oos operation mode
setting option is
“Way out” or “Adaptive”.
Section 4
1MAC059074-MB A
Protection functions
688
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......