![background image](http://html.mh-extra.com/html/abb/relion-615-series/relion-615-series_technical-manual_23951177.webp)
Description
Value
•
Control voltage range
20...250 V AC/DC
•
Current drain through the supervision circuit
~1.5 mA
•
Minimum voltage over the TCM contact
20 V AC/DC (15...20 V)
Table 985:
Single-pole power output relays
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Table 986:
High-speed output HSO with BIO0007
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
6 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
5 A/3 A/1 A
Trip time
<1 ms
Reset
<20 ms, resistive load
Table 987:
Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
Front
TCP/IP
protocol
Standard Ethernet CAT 5 cable with RJ-45
connector
10 MBits/s
Rear
TCP/IP
protocol
Shielded twisted pair CAT 5e cable with RJ-45
connector or fiber optic cable with LC connector
100 MBits/s
1MAC059074-MB A
Section 14
Technical data
615 series ANSI
1171
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......