![background image](http://html.mh-extra.com/html/abb/relion-615-series/relion-615-series_technical-manual_2395193.webp)
Table 182:
Station authority level “L,S,R” using CONTROL function block
L/R Control
L/R Control status
Control access
Control FB input CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850
client
2)
IEC 61850
client
3)
CTRL_OFF
FALSE
FALSE
0
CTRL_LOC
FALSE
FALSE
1
x
CTRL_STA
TRUE
FALSE
3
x
CTRL_REM
4)
TRUE
FALSE
3
x
CTRL_REM
FALSE
FALSE
2
x
CTRL_ALL
FALSE
FALSE
0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.17.10.7
Station authority level “L,S,S+R,L+S,L+S+R”
Station authority level “L,S,S+R,L+S,L+S+R” adds station control access together with
several different multilevel access scenarios. Control access can also be simultaneously
permitted from local, station or remote location. Simultaneous local, station or remote
control operation is not allowed as one client and location at time can access controllable
objects and they remain reserved until the previously started control operation is first
completed by the client.
IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
L+S
LOCAL
STATION
S+R
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
OFF
L+S+R
GUID-3F4E6CD7-A89E-4057-8E25-8846B5387C82 V1 EN
Figure 96:
Station authority is “L,S,S+R,L+S,L+S+R”
When station authority level “L,S,S+R,L+S,L+S+R” is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input
CTRL_STA
are applicable for
this station authority level.
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
187
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......