![background image](http://html.mh-extra.com/html/abb/relion-615-series/relion-615-series_technical-manual_23951108.webp)
t[s] Reset time (in seconds)
k
set
Time multiplier
I
Measured current
I>
set
Pickup value
Table 945:
Coefficients for ANSI delayed inverse reset curves
Curve name
D
(1) ANSI Extremely Inverse
29.1
(2) ANSI Very Inverse
21.6
(3) ANSI Normal Inverse
0.46
(4) ANSI Moderately Inverse
4.85
(6) Long Time Extremely Inverse
30
(7) Long Time Very Inverse
13.46
(8) Long Time Inverse
4.6
Section 11
1MAC059074-MB A
General function block features
1102
615 series ANSI
Technical Manual