the neutral current IG_2H / IG. Typically, the second harmonic content of the neutral
current at the magnetizing inrush is higher than that of the phase currents.
4.3.3.6
Signals
Table 442:
87LOZREF Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
IG
SIGNAL
0
Zero-sequence current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 443:
87LOZREF Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip
PICKUP
BOOLEAN
Pickup
BLK2H
BOOLEAN
2nd harmonic block
4.3.3.7
Settings
Table 444:
87LOZREF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Trip value
5.0...50.0
%In
1.0
5.0
Trip value
Table 445:
87LOZREF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum trip time
40...300000
ms
1
40
Minimum trip time
Restraint mode
1=None
2=Harmonic2
1=None
Restraint mode
Pickup value 2.H
10...50
%
1
50
The ratio of the 2. harmonic to fundamental
component required for blocking
Section 4
1MAC059074-MB A
Protection functions
548
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......