The lower part of
shows the voltage balance when there is no fault in the system
and no CT saturation.
I
d
R
s
R
m1
R
in1
R
in2
R
m2
E
1
V
E
2
V
≈
0
E
1
E
2
GUID-FC2F69DB-84BE-4597-B6E6-21860755CC50 V1 EN
Figure 279:
Equivalent circuit when there is no fault or CT saturation
When there is no fault, the CT secondary currents and their emf voltages, E
1
and E
2
, are
opposite and the protection relay measuring branch has no voltage or current. If an in-zone
fault occurs, the secondary currents have the same direction. The relay measures the sum
of the currents as a differential and trips the circuit breaker. If the fault current goes
through only one CT, its secondary emf magnetizes the opposite CT, that is, E
1
≈ E
2
.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
555
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......