Settings
Curve A
Curve B
Voltage level 4
-
0.9 · Un
Recovery time 4
-
1500 ms
Voltage level 5
-
0.9 · Un
Recovery time 5
-
3000 ms
It is necessary that the last active
Voltage level X
setting is set greater than
or equal to
Voltage pickup value
. Settings are not accepted if the last active
Voltage level X
setting is not set greater than or equal to
Voltage pickup
value
.
describes an example of operation of 27RT protection function set to operate
with
Num of pickup phases
set to “Exactly 2 of 3” and
Voltage selection
as “Lowest Ph-
to-Ph” voltage.
Time in ms
Vn
Voltage
xVn
TRIP
PICKUP
Voltage pickup value
PICKUP
Num of start phases =
Exactly 2 of 3
Voltage selection
= Lowest Ph-to-Ph
TRIP
V_AB
V_CA
V_BC
100ms
GUID-532E4687-DF59-4DA7-9F93-6186FBA14C64 V1 EN
Figure 331:
Typical example of operation of 27RT function
Activation of the
BLOCK
input resets the timers and deactivates the function outputs.
Section 4
1MAC059074-MB A
Protection functions
662
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......