Level detector 1
The measured phase currents are compared phasewise to the set
Current value
. If the
measured value exceeds the set
Current value
, the level detector reports the exceeding of
the value to the start, retrip and backup trip logics. The parameter should be set low enough
so that breaker failure situations with small fault current or high load current can be
detected. The setting can be chosen in accordance with the most sensitive protection
function to start the breaker failure protection.
Level detector 2
The measured residual current is compared to the set
Current value Res
. If the measured
value exceeds the set
Current value Res
, the level detector reports the exceeding of the
value to the pickup and backup trip logics. In high-impedance grounded systems, the
residual current at phase-to-ground faults is normally much smaller than the short circuit
currents. To detect a breaker failure at single-phase ground faults in these systems, it is
necessary to measure the residual current separately. In effectively grounded systems,
also the setting of the ground-fault current protection can be chosen at a relatively low
current level. The current setting should be chosen in accordance with the setting of the
sensitive ground-fault protection.
Start logic
The start logic is used to manage the starting of the timer 1 and timer 2. It also resets the
function after the circuit breaker failure is handled. On the rising edge of the
PICKUP
input, the enabling signal is send to the timer 1 and timer 2.
Function resetting is prevented during the next 150 ms. The 150 ms time elapse is
provided to prevent malfunctioning due to oscillation in the starting signal.
In case the setting
Pickup latching mode
is set to "Level sensitive", the 50BF is reset
immediately after the
PICKUP
signal is deactivated. The recommended setting value is
"Rising edge".
The resetting of the function depends on the
CB failure mode
setting.
•
If
CB failure mode
is set to "Current", the resetting logic further depends on the
CB
failure trip mode
setting.
Section 5
1MAC059074-MB A
Protection related functions
774
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......