The frequent operation counter limit is reached and new sequence is initiated. The
lockout is released when the recovery timer elapses.
•
The protection trip signal has been active longer than the time set with the
Max wait
time
parameter since the shot initiation.
•
The circuit breaker is closed manually during an autoreclosing sequence and the
manual close mode is FALSE.
9.4.4.6
Protection coordination controller
The
PROT_CRD
output is used for controlling the protection functions. In several
applications, such as fuse-saving applications involving down-stream fuses, tripping and
initiation of shot 1 should be fast (instantaneous or short-time delayed). The tripping and
initiation of shots 2, 3 and definite tripping time should be delayed.
In this example, two overcurrent elements 51P and 50P-2 are used. 50P-2 is given an
instantaneous characteristic and 51P is given a time delay.
The
PROT_CRD
output is activated, if the
SHOT_PTR
value is same or higher than the
value defined with the
Protection crd limit
setting and all initialization signals have been
reset. The
PROT_CRD
output is reset under the following conditions:
•
If the cut-out time elapses
•
If the reclaim time elapses and the AR function is ready for a new sequence
•
If the AR function is in lockout or disabled, that is, if the value of the
Protection crd
mode
setting is "AR inoperative" or "AR inop, CB man".
The
PROT_CRD
output can also be controlled with the
Protection crd mode
setting. The
setting has the following modes:
•
"no condition": the
PROT_CRD
output is controlled only with the
Protection crd limit
setting
•
"AR inoperative": the
PROT_CRD
output is active, if the AR function is disabled or
in the lockout state, or if the
INHIBIT_RECL
input is active
•
"CB close manual": the
PROT_CRD
output is active for the reclaim time if the circuit
breaker has been manually closed, that is, the AR function has not issued a close
command
•
"AR inop, CB man": both the modes "AR inoperative" and "CB close manual" are
effective
•
"always": the
PROT_CRD
output is constantly active
Section 9
1MAC059074-MB A
Control functions
1008
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......