![background image](http://html.mh-extra.com/html/abb/relion-615-series/relion-615-series_technical-manual_2395705.webp)
Offset
Displacement
Diameter
X (Reactance) p.u.
R (Resistance) p.u.
-R
-X
Operating Region
GUID-A023B281-CA68-4A0C-8E90-9075DF588504 V2 EN
Figure 347:
Operating region of the impedance mho circle
A fault in Automatic Voltage Regulator (AVR) or in the excitation system may cause a
total loss of excitation. A short circuit on the slip rings reduces the excitation voltage to
zero. This causes a gradual reduction of the excitation current and eventually a loss of
excitation. An open circuit in the field circuit also causes a loss of excitation. These are
typical examples which cause underexcitation in synchronous machines. This module
detects the underexcitation condition for the above cases when the calculated impedance
enters the operating characteristics.
External loss detection
The module checks the status information of the excitation system. It is activated when the
External Los Det Ena
setting is set to "Enable". The total loss of excitation current or a
failure in the excitation system is indicated by connecting the external binary signal to the
EXT_LOS_DET
input. The Timer is enabled immediately when the
EXT_LOS_DET
input is activated.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
699
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......