Furthermore, the DC time constant (T
dc
) of the fault current is now smaller, assumed
to be 50 ms here.
Assuming the maximum fault current is 30 percent lower than in the bus fault and a
DC offset 90 percent of the maximum.
Ik
max
= 0.7 × 6 = 4.2 (I
R
)
T
dc
= 50 ms
ω
= 100π Hz
T
m
= 10 ms
K
r
= 1/(1-0.4) = 1.6667
with these values gives the result:
F
K
Ik
T
e
a
r
dc
T
m
Tdc
>
×
×
×
×
×
−
+
≈
−
max
.
(
(
)
)
0 9
1
1
24
ω
GUID-46A4591B-876D-4E32-A9AB-29F6C1657644 V2 EN
If the actual burden of the current transformer S
a
in the accuracy limit factor equation
cannot be reduced low enough to provide a sufficient value for F
a
, there are two
alternatives to deal with the situation.
1. A current transformer with a higher rated burden S
n
can be chosen (which also means
a higher rated accurate limit F
n
).
2. A current transformer with a higher nominal primary current I
1n
(but the same rated
burden) can be chosen.
Alternative 2 is more cost-effective and therefore often better, although the sensitivity of
the scheme is slightly reduced.
Example 2
Here the actions according to alternative 2 are taken to improve the actual accuracy limit
factor.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
579
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......