Section 5
Protection related functions
5.1
Three-phase inrush detector INR
5.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase inrush detector
INRPHAR
3I2f>
INR
5.1.2
Function block
A070377-ANSI V1 EN
Figure 384:
Function block
5.1.3
Functionality
The three-phase inrush detector function INR is used to coordinate transformer inrush
situations in distribution networks.
Transformer inrush detection is based on the following principle: the output signal
BLK2H
is activated once the numerically derived ratio of second harmonic current I_2H and the
fundamental frequency current I_1H exceeds the set value.
The trip time characteristic for the function is of definite time (DT) type.
The function contains a blocking functionality. Blocking deactivates all outputs and resets
timers.
1MAC059074-MB A
Section 5
Protection related functions
615 series ANSI
767
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......