apparatus fails to enter the correct state, the output pulse is deactivated after the set
Operation timeout
setting, and an error message is displayed. When the
Adaptive pulse
is
set to “FALSE”, the functions always use the maximum pulse width, defined by the user-
configurable
Pulse length
setting. The
Pulse length
setting is the same for both the
opening and closing commands. When the apparatus already is in the right position, the
maximum pulse length is given.
The
Pulse length
setting does not affect the length of the trip pulse.
Control methods
The command execution mode can be set with the
Control model
setting. The alternatives
for command execution are direct control and secured object control, which can be used
to secure controlling.
The secured object control SBO is an important feature of the communication protocols
that support horizontal communication, because the command reservation and
interlocking signals can be transferred with a bus. All secured control operations require
two-step commands: a selection step and an execution step. The secured object control is
responsible for the several tasks.
•
Command authority: ensures that the command source is authorized to operate the
object
•
Mutual exclusion: ensures that only one command source at a time can control the
object
•
Interlocking: allows only safe commands
•
Execution: supervises the command execution
•
Command canceling: cancels the controlling of a selected object.
In direct operation, a single message is used to initiate the control action of a physical
device. The direct operation method uses less communication network capacity and
bandwidth than the SBO method, because the procedure needs fewer messages for
accurate operation.
The “status-only” mode means that control is not possible (non-controllable) via
communication or from LHMI. However, it is possible to control a disconnector (29DC)
from
AU_OPEN
and
AU_CLOSE
inputs.
AU_OPEN
and
AU_CLOSE
control the object directly regardless of the set
Control model
. These inputs can be used when control is wanted to be
implemented purely based on ACT logic and no additional exception
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
963
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......