3.17.2.2
Minimum pulse timer 62TPS
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum second pulse timer (2 pcs)
TPSGAPC
TPS
62TPS
Function block
62TPS
OUT2
OUT1
IN1
IN2
GUID-F47E9742-1C94-4E8E-B2D8-CC9F3A8FE0EF V1 EN
Figure 78:
Function block
Functionality
The Minimum second pulse timer function 62TPS contains two independent timers. The
function has a settable pulse length (in seconds). The timers are used for setting the
minimum pulse length for example, the signal outputs. Once the input is activated, the
output is set for a specific duration using the
Pulse time
setting. Both timers use the same
setting parameter.
GUID-9BE17BA5-70D3-442B-8D24-8544C7A9441A V1 EN
Figure 79:
A = Trip pulse is shorter than Cold load time setting, B = Trip pulse is
longer than Cold load time setting
Signals
Table 145:
62TPS Input signals
Name
Type
Default
Description
IN1
BOOLEAN
0=False
Input 1
IN2
BOOLEAN
0=False
Input 2
Section 3
1MAC059074-MB A
Basic functions
166
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......