-VG
IG
GUID-A41E27BC-B5F2-4B8C-891D-BEF592013BEB V1 EN
Figure 158:
Configurable operating sectors in phase angle characteristic
Table 351:
Momentary operating direction
Fault direction
The value for DIRECTION
Angle between the polarizing and operating quantity
is not in any of the defined sectors.
0 = unknown
Angle between the polarizing and operating quantity
is in the forward sector.
1= forward
Angle between the polarizing and operating quantity
is in the reverse sector.
2 = backward
Angle between the polarizing and operating quantity
is in both the forward and the reverse sectors, that is,
the sectors are overlapping.
3 = both
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
341
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......