Table 905:
Settings for configuration example 1
Setting name
Setting value
Shot number CBB1
1
Init signals CBB1
7 (lines 1, 2 and 3 = 1+2+4 = 7)
First reclose time
0.3s (an example)
Shot number CBB2
2
Init signals CBB2
7 (lines 1, 2 and 3 = 1+2+4 = 7)
Second reclose time
15.0s (an example)
Example 2
There are two separate sequences implemented with three shots. Shot 1 is implemented by
CBB1 and it is initiated with the high stage of the overcurrent protection (50P-1). Shot 1
is set as a high-speed autoreclosing with a short time delay. Shot 2 is implemented with
CBB2 and meant to be the first shot of the autoreclose sequence initiated by the low stage
of the overcurrent protection (51P) and the low stage of the non-directional ground-fault
protection (51N/G). It has the same reclose time in both situations. It is set as a high-speed
autoreclosing for corresponding faults. The third shot, which is the second shot in the
autoreclose sequence initiated by 51P or 51N/G, is set as a delayed autoreclosing and
executed after an unsuccessful high-speed autoreclosing of a corresponding sequence.
1MAC059074-MB A
Section 9
Control functions
615 series ANSI
1021
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......