3.7
Test mode
3.7.1
Function blocks
GUID-DFF8F71A-895C-4C06-B287-63C3CA26154C V2 EN
GUID-FA386432-3AEF-468D-B25E-D1C5BDA838E3 V3 EN
Figure 20:
Function blocks
3.7.2
Functionality
The mode of all the logical nodes in the relay's IEC 61850 data model can be set with
Test
mode
.
Test mode
is selected through one common parameter via the WHMI path
Tests/IED test
. By default,
Test mode
can only be set locally through LHMI.
Test mode
is
also available via IEC 61850 communication (LD0.LLN0.Mod).
Table 37:
Test mode
Test mode
Description
Protection BEH_BLK
Normal mode
Normal operation
FALSE
IED blocked
Protection working as in “Normal mode” but ACT
configuration can be used to block physical outputs
to process. Control function commands blocked.
TRUE
IED test
Protection working as in “Normal mode” but
protection functions are working in parallel with test
parameters.
FALSE
IED test and blocked
Protection working as in “Normal mode” but
protection functions are working in parallel with test
parameters. ACT configuration can be used to block
physical outputs to process. Control function
commands blocked.
TRUE
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
89
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......