GUID-82695BC5-1E26-4AF4-97D9-252671CF972F V1 EN
Figure 399:
Block diagram of HIZ
HIZ is based on algorithms that use ground current signatures which are considered non-
stationary, temporally volatile and of various burst duration. All harmonic and non-
harmonic components within the available data window can play a vital role in the high-
impedance fault detection. A major challenge is to develop a data model that
acknowledges that high-impedance faults could take place at any time within the
observation window of the signal and could be delayed randomly and attenuated
substantially. The model is motivated by extensive research, actual experimental
observations in the laboratory, field testing and what traditionally represents an accurate
depiction of a non-stationary signal with a time-dependent spectrum.
GUID-61D297F5-783F-4CF2-BD16-18CE537C9E95-ANSI V1 EN
Figure 400:
Validation of HIZ on gravel
GUID-B9AC5923-6A67-431B-A785-171FD132E1A6-ANSI V1 EN
Figure 401:
Validation of HIZ on
concrete
1MAC059074-MB A
Section 5
Protection related functions
615 series ANSI
791
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......