-VG (Polarizing quantity)
VG
Backward
area
Forward
area
IG (Operating quantity)
Zero torque line
Minimum
operate current
Maximum torque line
forward direction (RCA = 0
˚
)
Maximum torque line
reverse direction (RCA = 0
˚
)
Forward
area
Backward
area
GUID-CA5E7641-C50F-4303-B101-70181A1F3071 V1 EN
Figure 198:
Definition of the relay characteristic angle
The phase angle difference is calculated based on the
Characteristic angle
setting (also
known as Relay Characteristic Angle (RCA) or Relay Base Angle or Maximum Torque
Angle (MTA)). The
Characteristic angle
setting is done based on the method of
grounding employed in the network. For example, in case of an ungrounded network, the
Characteristic angle
setting is set to -90°, and in case of a compensated network, the
Characteristic angle
setting is set to 0°. In general,
Characteristic angle
is selected so that
it is close to the expected fault angle value, which results in maximum sensitivity.
Section 4
1MAC059074-MB A
Protection functions
412
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......