GUID-74289FF5-E90D-4633-9FEE-04DB8E86A3AE V1 EN
Figure 227:
Example of CT ratio correction setting calculation with in-zone
transformer
The rated load of the transformer is:
HV side (A): I
nT_A
= 5 MVA / (1.732 × 20 kV) = 144.3 A
LV side (A): I
nT_B
= 5 MVA / (1.732 × 10.5 kV) = 274.9 A
So the settings for
CT ratio Corrections
at HV (A) and LV (B) side are:
CT ratio Correction (A) = 200 A / 144.3 A = 1.386
CT ratio Correction (B) = 300 A / 274.9 A = 1.091
CT connections
The connections of the primary current transformers are designated as “Type 1” and
“Type 2”.
•
If the positive directions of the winding 1 and winding 2 protection relay currents are
opposite, the
CT connection type
setting parameter is “Type 1”. The connection
examples of “Type 1” are as shown in the
•
If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the
CT connection type
setting parameter is “Type 2”. The connection
examples of “Type 2” are as shown in the
•
The default value of the
CT connection type
setting is “Type 1”.
Section 4
1MAC059074-MB A
Protection functions
468
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......