The calculated Iosin(φ) or Iocos(φ) current used in direction determination can be read
through the
I_OPER
monitored data. The value can be passed directly to a decisive
element, which provides the final pickup and trip signals.
The
I_OPER
monitored data gives an absolute value of the calculated
current.
The following examples show the characteristics of the different operation criteria:
Example 1.
Iosin(φ) criterion selected, forward-type fault
=> FAULT_DIR = 1
IG
IGsin
Forward
tripping zone
Backward
tripping zone
-VG
Correction
angle
non-
tri
p
pi
ng
zone
Min operating
current
RCA
= -90 deg
GUID-BC040813-ECB4-4D8C-9329-6CA29EE239C7 V1 EN
Figure 159:
Operating characteristic Iosin(φ) in forward fault
The operating sector is limited by angle correction, that is, the operating sector is 180
degrees - 2*(angle correction).
Example 2.
Iosin(φ) criterion selected, reverse-type fault
=> FAULT_DIR = 2
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
343
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......