lower than with the protection core. This should be taken into account
when setting the current circuit supervision function.
CCM
I_A
I_B
ALARM
FAIL
I_C
I_REF
BLOCK
protection relay
Co
re
1
(p
ro
tection
)
IL1
IL2
IL3
I_A
I_B
I_C
I_REF
Measurement device
Co
re 2
(m
ea
su
re
me
nt)
GUID-C5A6BB27-36F9-4652-A5E4-E3D32CFEA77B-ANSI V3 EN
Figure 439:
Connection diagram for current circuit supervision with two sets of three-
phase current transformer cores (protection and measurement)
Example of incorrect connection
The currents must be measured with two independent cores, that is, the phase currents
must be measured with a different core than the reference current. A connection diagram
shows an example of a case where the phase currents and the reference currents are
measured from the same core.
1MAC059074-MB A
Section 6
Supervision functions
615 series ANSI
851
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......