8.1.4.3
Signals
Table 794:
IA,IB,IC Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for all binary outputs
Table 795:
IA,IB,IC Output signals
Name
Type
Description
HIGH_ALARM
BOOLEAN
High alarm
HIGH_WARN
BOOLEAN
High warning
LOW_WARN
BOOLEAN
Low warning
LOW_ALARM
BOOLEAN
Low alarm
8.1.4.4
Settings
Table 796:
IA,IB,IC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required by limit supervision
A high high limit
0.00...40.00
xIn
1
1.40
High alarm current limit
A high limit
0.00...40.00
xIn
1
1.20
High warning current limit
A low limit
0.00...40.00
xIn
1
0.00
Low warning current limit
A low low limit
0.00...40.00
xIn
1
0.00
Low alarm current limit
A deadband
100...100000
1
2500
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Table 797:
IA,IB,IC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement mode
1=RMS
2=DFT
2=DFT
Selects used measurement mode
1MAC059074-MB A
Section 8
Measurement functions
615 series ANSI
907
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......