The operation of 67/51N, 67/50N can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
0
0
A070438-ANSI V1 EN
Figure 151:
Functional module diagram
Level detector
The magnitude of the operating quantity is compared to the set
Pickup value
and the
magnitude of the polarizing quantity is compared to the set
Voltage pickup value
. If both
the limits are exceeded, the level detector sends an enabling signal to the timer module.
When the
Enable voltage limit
setting is set to "False",
Voltage pickup value
has no effect
and the level detection is purely based on the operating quantity. If the
ENA_MULT
input
is active, the
Pickup value
setting is multiplied by the
Pickup value Mult
setting.
The operating quantity (residual current) can be selected with the setting
IG/I0 signal Sel
.
The options are "Measured IG" and "Calculated I0". If "Measured IG" is selected, the
current ratio for IG-channel is given in
Configuration/Analog inputs/Current
(IG,CT)
. If "Calculated I0" is selected, the current ratio is obtained from the phase-current
channels given in
Configuration/Analog inputs/Current (3I,CT)
.
The operating quantity (residual voltage) can be selected with the setting
Vg or V0
The
options are "Measured VG" and "Calculated V0". If "Measured VG" is selected, the
voltage ratio for VG-channel is given in
Configuration/Analog inputs/Voltage
(VG,VT)
. If "Calculated V0" is selected, the voltage ratio is obtained from the phase-
voltage channels given in
Configuration/Analog inputs/Voltage (3V,VT)
.
Example 1
: IG is measured with cable core CT (100/1 A) and VG is measured from open-
delta connected VTs (20/sqrt(3) kV : 100/sqrt(3) V : 100/3 V). In this case, "Measured IG"
and "Measured VG" are selected. The nominal values for residual current and residual
voltage are obtained from CT and VT ratios entered in Residual current IG:
Configuration/Analog inputs/Current (IG,CT)
: 100 A : 1 A. The Residual voltage VG:
Configuration/Analog inputs/Voltage (VG,VT)
: 11.547 kV : 100 V. The
Pickup value
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
327
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......