The harmonics current I_HARM_RES is available in the monitored data view. The value
is also sent over horizontal communication to the other protection relays on the parallel
feeders configured in the protection scheme.
Nor
maliz
ed output
0.5
0
0
1.0
Frequency
2f
f
GUID-F05BA8C4-AC2B-420C-AE9D-946E815682D5 V1 EN
Figure 194:
High-pass filter
Level detector
The harmonics current is compared to the
Pickup value
setting. If the value exceeds the
value of the
Pickup value
setting, Level detector sends an enabling signal to the Timer
module.
Current comparison
The maximum of the harmonics currents reported by other parallel feeders in the
substation, that is, in the same busbar, is fed to the function through the
I_REF_RES
input. If the locally measured harmonics current is higher than
I_REF_RES
, the enabling
signal is sent to Timer.
If the locally measured harmonics current is lower than
I_REF_RES
, the fault is not in
that feeder. The detected situation blocks Timer internally, and simultaneously also the
BLKD_I_REF
output is activated.
The module also supervises the communication channel validity which is reported to the
Timer.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
403
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......