Table 136:
SR Output signals
Name
Type
Description
Q
BOOLEAN
Q status
NOTQ
BOOLEAN
NOTQ status
3.17.1.13
RS function block
Function block
GUID-3876F400-A7D1-45DA-B20F-DFA5AE863073 V1 EN
Figure 75:
Function block
Functionality
The RS flip-flop output
Q
can be set or reset from the
S
or
R
inputs.
R
input has a higher
priority over the
S
input. Output
NOTQ
is the negation of output
Q
.
The statuses of outputs
Q
and
NOTQ
are not retained in the nonvolatile
memory.
Table 137:
Truth table for RS flip-flop
S
R
Q
0
0
0
1)
0
1
0
1
0
1
1
1
0
1) Keep state/no change
Signals
Table 138:
RS Input signals
Name
Type
Default
Description
S
BOOLEAN
0=False
Set Q output when set
R
BOOLEAN
0=False
Resets Q output when
set
1MAC059074-MB A
Section 3
Basic functions
615 series ANSI
163
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......