program. The influence of the
BLOCK
input signal activation is preselected with the global
Blocking mode
setting.
The Blocking mode setting has three blocking methods. In the "Freeze timers" mode, the
operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block TRIP output" mode, the function
operates normally but the
TRIP
output is not activated.
4.5.9.5
Application
Systems with critical motor applications provide backup power sources to those motors
that can be switched in when an undervoltage on the original power source is detected. The
three-phase undervoltage protection 27R is used to monitor for an undervoltage condition
over a decaying frequency after original power is lost, before allowing re-application of
backup power. An independent undervoltage function, operating at nominal frequency,
can be used to detect the original loss of primary power and initiate the transfer to backup
power. 27R provides a permissive signal indicating when restoration of backup power can
be completed safely.
When the power to a motor is suddenly lost, the motor terminal voltage does not
immediately fall to zero but remains as the rotating motor now acts as a generator
producing its own voltage. This remnant voltage decays as the motor slows to a stop at a
rate depending on the motor and load. Applying the backup power source while the
remnant voltage is still present can result in damage to the motor shaft and windings.
27R operates over the range of 10...70 Hz so it can monitor the voltage while the motor is
slowing and prevent transfer of the backup power until the motor voltage has decayed to
a safe level. The undervoltage setting is typically set 20...30 percent of rated voltage.
There is also a time delay setting to ensure that the remnant voltage remains below the
undervoltage setting for the set time. 27R includes a settable value for the detection of
undervoltage in either a single phase, two phases, or in all three phases. This setting value
should always be set for three phases in the remnant undervoltage application but can be
changed if 27R is used as a standard undervoltage function.
The function contains a self-blocking functionality. It is possible to block function
outputs, timer or the function itself, if desired.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
675
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......