![background image](http://html.mh-extra.com/html/abb/relion-615-series/relion-615-series_technical-manual_2395953.webp)
Table 850:
RDRE Non-group channel settings
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=on
5=off
1
1=on
Analog
channel is
enabled or
disabled
Channel
selection
0=Disabled
1=IG
2=IA-A
3=IB-A
4=IC-A
5=IG2-A
6=IA2-A
7=IB2-A
8=IC2-A
9=VG-A
10=VA-A
11=VB-A
12=VC-A
13=VG2-A
14=VA2-A
15=VB2-A
16=VC2-A
17=CI0
18=SI1
1)
19=SI2
1)
20=SU0
21=SU1
1)
22=SU2
1)
23=CI0B
24=SI1B
1)
25=SI2B
1)
26=SUoB
27=SU1B
1)
28=SU2B
1)
29=V12
30=V23
31=V31
32=VA
33=VB
34=VC
35=V12B
36=V23B
37=V31B
38=VA-B
39=VB-B
40=VC-B
0
0=Disabled
Select the
signal to be
recorded by
this channel.
Applicable
values for this
parameter are
product variant
dependent.
Every product
variant
includes only
the values that
are applicable
to that
particular
variant
Channel id text
0 to 64
characters,
alphanumeric
DR analog
channel X
Identification
text for the
analog channel
used in the
COMTRADE
format
Table continues on next page
1MAC059074-MB A
Section 8
Measurement functions
615 series ANSI
947
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......