Figure 242:
Protection communication supervision detects failures on
communication
In-zone transformer
20kV
300A/1
1500A/1
PROTECTED
ZONE
110kV
Yd11
40MW
HV
LV
L
~
RED 615
RED 615
GUID-52FC4852-C9D1-4DD1-B2D7-62FCE98B7FD7 V2 EN
Figure 243:
In-zone transformer example about CT ratio correction calculation
The CT ratio correction calculation starts with the rated load current calculation for HV
and LV sides. The rated load current is defined as the rated power of the transformer
Section 4
1MAC059074-MB A
Protection functions
492
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......