Underimpedance protection for generators
The underimpedance protection is set to protect the zone between the generator windings
and the generator side windings of the step-up transformer. The function mainly protects
the generator bus, the low-voltage part of the step-up transformer and a part of the stator
winding against any short circuits.
The voltages should be measured from the generator terminals and the phase currents
from the neutral point of the generator.
GUID-E1B90616-E865-49E2-9366-616B0112CA85 V1 EN
Figure 356:
Current and voltage signals for underimpedance protection
To prevent malfunctioning of the underimpedance protection in case of nearby faults, the
Polar reach
setting is set to a value equal to 70 percent of the step-up transformer short
circuit impedance.
In directly connected machines where the impedance towards the network is limited only
by the lines or bus bars, it must be secured that the function does not cause any selectivity
problems. In such cases, it is recommended to use the voltage-dependent overcurrent
protection instead of the underimpedance protection.
Section 4
1MAC059074-MB A
Protection functions
714
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......