energization of a transformer running in parallel with the protected transformer connected
to the network.
The second harmonic blocking is disabled when
Restraint mode
is set to "None" and
enabled when set to "Harmonic2".
Timer
Once activated, the Timer activates the
PICKUP
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Minimum trip
time
, the
TRIP
output is activated. If the fault disappears before the module trips, the reset
timer is activated. If the reset timer reaches the value set by
Reset delay time
, the reset
timer resets and the
PICKUP
output is deactivated.
The Timer calculates the pickup duration value PICKUP_DUR which indicates the
percentage ratio of the pickup situation and the set trip time. The value is available through
the Monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in
Configuration/System/Blocking
mode
which selects the blocking mode. The
BLOCK
input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode, the
operate timer is frozen to the prevailing value, but the
TRIP
output is not deactivated
when blocking is activated. In the "Block all" mode, the whole function is blocked and the
timers are reset. In the "Block TRIP output" mode, the function operates normally but the
TRIP
output is not activated. The activation of the output of the second harmonic
blocking signal
BLK2H
deactivates the
TRIP
output.
4.3.3.5
Application
A ground-fault protection using an overcurrent element does not adequately protect the
transformer winding in general and the star-connected winding in particular.
The restricted ground-fault protection is mainly used as a unit protection for the
transformer windings. 80LOZREF is a sensitive protection applied to protect the star-
connected winding of a transformer. This protection system remains stable for all the
faults outside the protected zone.
87LOZREF provides higher sensitivity for the detection of ground faults than the overall
transformer differential protection. This is a high-speed unit protection scheme applied to
Section 4
1MAC059074-MB A
Protection functions
542
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......