Testing of the line differential protection is done with both protection relays separated
geographically from each other. It is important to note that local actions in one protection
relay cause operation also in the remotely located protection relay. When testing the line
differential function, actions have to be done in both protection relays.
Before the test, the trip signal to the circuit breaker shall be blocked, for example by
breaking the trip circuit by opening the terminal block or by using some other suitable
method.
When injecting current to one phase in the local end protection relay, the current is seen
as a differential current at both ends. If a current I
injected
is injected, A in phase A, the
differential and stabilizing currents for phase A are:
ID
A
I
injected
_
=
GUID-B5B84B9B-B26C-421F-B4D0-E301EE4883F3 V3 EN
(Equation 78)
IB
A
I
injected
_
/
=
2
GUID-6A1A367B-241B-4831-A1F2-9373AE4D26ED V1 EN
(Equation 79)
The operation is equal for phases B and C.
Verifying the settings
1.
Block the unwanted trip signals from the protection relay units involved.
2.
Inject a current in phase A and increase the current until the function operates for
phase A.
The injected operate current corresponds to the set
Low operate value
. The
monitored values for ID_A should be equal to the injected current.
3.
Repeat point 2 by current injection in phases B and C.
4.
Measure the operating time by injecting the single-phase current in phase A.
The injected current should be four times the operating current. The time
measurement is stopped by the trip output from the protection relay unit.
5.
Disconnect the test equipment and reconnect the current transformers and all other
circuits including the trip circuit.
Phasor echoing method
The line differential function in one protection relay can be set to special test mode, that
is, the
Operation
setting is set to “test/blocked”. When this mode is in use, the remote end
protection relay echoes locally injected current phasors back with the shifted phase and
settable amplitude. Therefore, the local end line differential function is also automatically
blocked and the remote end line differential function discards the phasors it receives from
the protection relay in the test mode.
When the test mode is active, the
CT connection type
is still used by the line differential
protection function as in the normal operation mode. The setting can be used for shifting
the phase (0 or 180 degrees).
Section 4
1MAC059074-MB A
Protection functions
488
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......