Figure 241:
Line differential applications
Communication supervision
A typical line differential protection application includes 87L as the main protection.
Backup over current functions is needed if a protection communication failure occurs.
When the communication supervision function detects a failure in the communication
between the protective units, the safe operation of the line is still guaranteed by blocking
the line differential protection and unblocking the over current functions.
When a communication failure is detected, the protection communication supervision
function issues block for the 87L line differential protection and unblock for the
instantaneous and high stages (instance 2) of the over current protection. These are used
to give backup protection for the remote end feeder protection relay. In situations where
the selectivity is weaker than usually, the protection should still be available for the
system.
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
491
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......