function is blocked and the timers are reset. In the "Block TRIP output" mode, the function
operates normally but the
TRIP
output is not activated.
Timer
If the detected fault direction is opposite to the set directional mode and GFC release is
active,
BLK_EF
output is activated once
Pickup delay time
has elapsed. Reset timer is
activated at the falling edge of General Fault Criterion release, that is, when zero-sequence
voltage falls below
Voltage pickup value
. BLK_EF is reset once the reset delay time
elapses. Activation of the
BLOCK
input deactivates the
BLK_EF
output and resets Timer.
GFC
release
Reset
timer
BLK_EF
Pickupt
delay
time
Pickup
delay
time
Reset
delay
time
Reset
delay
time
IG
VG
GUID-A2A55E4C-395C-43BB-A942-2991EA37E3A4 V1 EN
Figure 219:
Activation of BLK_EF output (indication that fault is located opposite to
the set operate direction)
Section 4
1MAC059074-MB A
Protection functions
456
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......