The closing signal is delivered only once for each activated external closing command
signal. The pulse length of the delivered closing is set with the
Close pulse
setting.
t = Close pulse
GUID-0D9A1A7F-58D1-4081-B974-A3CE10DEC5AF V2 EN
Figure 496:
Determination of the pulse length of the closing signal
In the command control mode operation, there are alarms for a failed closing attempt
(
CL_FAIL_AL
) and for a command signal that remains active too long
(
CMD_FAIL_AL
).
If the conditions for closing are not fulfilled within the set time of
Maximum Syn time
, a
failed closing attempt alarm is given. The
CL_FAIL_AL
alarm output signal is pulse-
shaped and the pulse length is 500 ms. If the external command signal is removed too
early, that is, before conditions are fulfilled and the closing pulse is given, the alarm timer
is reset.
Section 9
1MAC059074-MB A
Control functions
982
615 series ANSI
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......