A2-13
IM 34M06C11-01E
Note
LG terminal has a half potential of the input power supply voltage when LG terminal isn’t
connected to earth appropriately.
Terminal dimensions
FA020304.VSD
7.1mm
8.2mm
M3.5
F3PU10-0N / F3PU20-0N
7.1mm
8.2mm
M4
F3PU10-0S / F3PU20-0S
Adaptable crimp-on terminal
Vendor
Model
Compatible Conductor
Compatible Modules and
Crimping Torque
F3PU10-0N
F3PU20-0N
F3PU10-0S
F3PU20-0S
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M3
AWG22 to 18
(0.33 to 0.82mm
2
)
(Copper wire)
0.8N
m
(7.1 lbf
in)
May not be
used
Nippon Tanshi Co., Ltd.
RAV1.25-3.5
Japan Solderless
Terminal Mfg Co., Ltd.
V1.25-M4
1.2N
m
(10.6 lbf
in)
Japan Solderless
Terminal Mfg Co., Ltd.
V2-M4
AWG16 to 14
(1.3 to 2.1mm
2
)
(Copper wire)
Note
When crimping terminals, be sure only to use the tool specified by each terminal
manufacturer.
Once the power supply module is installed in the base module, both the FG terminal of
the power supply module and the signal ground (GND terminal of the module’s 5V
output) of the FA-M3 automatically come into contact with the metal chassis of the base
module. The FG terminal and the signal ground are isolated from each other inside the
power supply module.
For details on the grounding lines of the FA-M3, see subsection A3.3.2, “Grounding
Lines.”
Note
- F3PU10-0N (respectively F3PU20-0N) and F3PU10-0S (respectively F3PU20-0S)
have the same dimensions, internal circuitry and other characteristics, except that
F3PU10-0N (respectively F3PU20-0N) uses M3.5-screw terminals while F3PU10-0S
(respectively F3PU20-0S) uses M4-screw terminals.
- F3PU10-0N and F3PU20-0N are not CE Marking compliant.
F3PU10-0S and F3PU20-0S are CE Marking compliant.
- For compliance to CE Marking of the final product incorporating these modules,
F3PU10-0S or F3PU20-0S must be used.
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...