A3-20
IM 34M06C11-01E
A3.4
Noise Control Considerations
Separating Cables from Motive-power Lines
Route motive-power lines so that they are no closer than 20cm to the FA-M3 and all
signal lines connected to the FA-M3. If this is not feasible, route the motive-power lines
through a grounded metal conduit.
20 cm
or farther
20 cm or farther
FA-M3
GND
FA-M3
Metal conduit
Motive-power lines
FA030401.VSD
Figure A3.17 Example of Separating Cables from Motive-power Lines
Protecting Power Supply Module against Noise
- Form the power line into a twisted pair and route it through the shortest distance
possible.
-
The power supply module of the FA-M3 contains a noise filter and therefore has a
noise immunity level sufficient for noise levels anticipated in general applications.
If the module is to be used in an exceptionally noisy environment however, an
additional ferrite core , noise filter or a noise cutoff transformer should be located
between the power source and the module.
Figure A3.18 Example of Power Supply Circuit Noise Control
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...