A4-8
IM 34M06C11-01E
Note
- If you want to reset the contacts of an output module in the event of a major or
moderate sequence CPU module failure, do the following: Use an output module
with 32 or less points and set the Output When Stopped field under "Input/Output
Setup" of the Configuration to "RESET". (For F3SP22/28/38/53/58/59/66/67/71/76
modules, F3YD64-1F, F3YD64-1P, F3YD64-1R, F3WD64-
□
F and F3WD64-
□
P
modules can also be used.)
- If you want to hold the contacts of an output module in the case of a major or
moderate sequence CPU module failure, set the Output When Stopped field under
"Input/Output Setup" of the Configuration to "HOLD". The behavior is independent
of the type of CPU module or output module.
Table A4.3 Failure Severity Levels and LED Indications
(when the CPU module is F3BP20 or F3BP30)
Severity
Level
LED
Indication
Effect Probable
Cause
Status of FAIL-signal
Contact Output
Status of Output Module
Between
FAIL1
and COM
Between
FAIL2
and COM
Output modules
other than
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N,
Y
□□□□□
*2
Major
Green RDY
lamp if off.
Key
hardware is
disabled.
• CPU error
• Memory crash
Shorted
Open
Default: HOLD
Can be set on a
8-point basis.
(in a CONTROL
statement)
Cannot be set
The status is
always HOLD
Moderate Red ERR
lamp is lit.
The user
program
cannot be
started or
run any
further.
• Program error
• I/O module error
P
*1
• BASIC error stop
(no ON ERROR)
• Startup error
• Invalid instruction found
• Number of I/O points
exceeded
• ROM pack error
• Subroutine error
P
*1
• Interrupt error
P
*1
• Subunit communication
error
Open
Shorted
Cannot be set
The status is
always HOLD
Cannot be set
The status is
always HOLD
Minor
Yellow
ALM
P
*1
P
lamp
is lit.
The program
can still run
In spite of a
minor failure
detected.
•
Momentary power
failure
P
*3
•
I/O module error
(during interrupt
processing)
Open
Shorted
Operation
continues
Operation
continues
*1:
The yellow ALM LED is also lit when the FA-M3 is in Debug mode.
*2:
Output relays (Y
□□□□□
) of the advanced modules.
*3:
When supply voltage abnormality is detected, output modules behave differently depending on whether the standard
mode or immediate detection mode is selected. Behaviors during momentary power failure in each mode are as
follows:
Supply Voltage
Abnormality
Detection mode
Status of FAIL-signal Contact Output
Status of Output Module
Between FAIL1 and
COM
Between FAIL2 and
COM
Output modules
other than
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N
F3YD64-1A,
F3YD64-1M,
F3WD64-
□
N,
Y
□□□□□
*2
Standard mode
Open
Shorted
Hold
Hold
Immediate
detection mode
Shorted
Open
Reset
Hold
Summary of Contents for FA-M3V e-RT3 Plus
Page 2: ...Blank Page ...
Page 14: ...Blank Page ...
Page 20: ...Blank Page ...
Page 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Page 22: ...Blank Page ...
Page 34: ...Blank Page ...
Page 160: ...Blank Page ...
Page 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Page 220: ...Blank Page ...
Page 232: ...Blank Page ...
Page 242: ...Blank Page ...
Page 252: ...Blank Page ...
Page 254: ...Blank Page ...
Page 268: ...Blank Page ...
Page 274: ...Blank Page ...